FIRE ALARM LINES
- Maximum number of fire detectors in a line
32
- Connecting line
two-wire
- Maximum resistance of a line
100Ω
CONTROLLABLE OUTPUTS
- Type
Potential
- Electrical characteristics
(24±5)V/500 mA
RELAY OUTPUTS FOR FAULT CONDITIONS
- Type
potential free, switching
- Electrical characteristics
3 A/125 V AC; 3 A/30 V DC
RELAY OUTPUTS FOR FAULT CONDITIONS
- Type
potential free, switching
- Electrical characteristics
3 A/125 V AC; 3 A/30 V DC
INDICATIONS OF REGISTERED EVENTS
- Light indication
LEDs
- Text messages
LCD display - 4 lines, 20 symbols,
Latin/Cyrillic characters, backlit
- Sound
Built-in sounder
ACCESS LEVELS TO CONTROL FUNCTIONS
4 (in compliance with EN 54/2)
POWER SUPPLY
- Voltage
220/230 V
- Frequency
50 Hz
BACKUP BATTERIES
2 x 12 V / 12 Ah
OPERATION IN DUTY MODE UPON INTERRUPTED MAINS SUPPLY
- Minimum configuration
80 h
- Maximum configuration
30 h
CONSUMPTION ON BACKUP BATTERIES SUPPLY IN DUTY MODE AT 24 V
- Minimum configuration
<155 mA
- Maximum configuration
<400 mA
POWER SUPPLY TO EXTERNAL DEVICES
- Voltage
(24±5)V
- Maximum current value (current of controllable outputs included)
1,5 A
WEIGHT (BACKUP BATTERIES NOT INCLUDED)
6,6 kg
DIMENSIONS
450 x 355 x 115mm
OPERATING TEMPERATURE
-5 oC to +40 oC
RELATIVE HUMIDITY
to 93 %
DEGREE OF PROTECTION
|